Current Location:
8-channel Analog Input/Thermocouple Input Module

Main Features

8-channel differential analog input module support Modbus protocol and ASCII protocol,
each channel range can be set independently
Input Channel: 8 channel analog input module
Input Type: thermocouple
Input Type: mV,V,4-20mA
Thermocouple Type: J,K,T,E,R,S,B,N,W
Sampling Rate: 10/S
Bandwidth:15.7Hz
Accuracy:±0.1%
Zero Drift:0.5uV/℃
Span Drift:15ppm/℃
CMR@50/60Hz:150dB

NMR@50/60Hz:100dB
Input Impedance:20M Ohms
Over Voltage Protection:±51V
Power:
Input:+4.5V ~ +55VDC
Power Dissipation:1.5W
Temperature:-20℃ ~ 70℃
Humidity:5% ~ 90%, no condensation

Product OverviewSpecificationOrdering Information

RemoDAQ-8018E

8 channel differential analog input modulewhich support Modbus and ASCII protocol,

its features are given asfollowing:

l   Software calibration

l   24-bit Sigma-Delta ADC providesextremely high accuracy

l   Built-in CJC, can be directlyconnected to the thermocouple

l   Different input ranges can be set fordifferent channels

l   broken thermocouple detection function


InputChannel:

8 channelanalog input module

Input Type:thermocouple

Input Type:mV, V, mA

SamplingRate:10 /S

Bandwidth:15.7Hz

Accuracy:±0.1%

Zero Drift:0.5uV/℃

          Span Drift:15ppm/℃

         CMR@50/60Hz:150dB

          NMR@50/60Hz:100dB

          Input Impedance:20M Ohms

          Over Voltage Protection:±51V

          Power

          Input:+4.5V ~ +55VDC

          Power Consumption:1.5W

          Temperature:-20℃~ 70℃

          Humidity:5% ~ 90%, no condensation