8 Channel Analog/ Thermocouple Input Module

Main Features
- Resolution: 16-bit
- Analog Input: Thermocouple, mV, V or mA
- Input Range: ±15mV, ±50mV, ±100mV, ±500mV,
±1V, ±2.5V, ±20mA
- Thermocouple Type: J, K, T, E, R, S, B, N, WRe5/26,L,M
- Channel: 6 channel differential/ 2 channel single-ended or
8 channel differential (jumper select)
- Sampling Rate: 10Hz
- With Thermocouple disconnection detection
- Support ASCII and Modbus protocol

 Bandwidth:15.7 Hz
 Accuracy:±0.1%
 Zero Drift:0.5µV/°C
 Span Drift:25ppm/°C
 CMR@50/60Hz:150dB
 NMR@50/60Hz:100dB
 Input Impedance:20M Ohms
 Fault and over-voltage protection:With stands over-voltage up to ±35V
 Isolation:3000VDC
 Power Consumption:1.0W
 Power Input: +10V ~ +30VDC
 Environment:
Operating Temperature : -20 ~ 70° C
Humidity: 5 ~ 95%, non-condensing
Product OverviewSpecificationOrdering Information

RemoDAQ-8018BL is an 8channel thermocouple input module,

thecommon features of AI modules are given as following:

l   3000VDC Isolated analog input.

l   24-bits sigma-delta ADC to provide excellent accuracy.

l   Thermocouple direct connect with build-in CJC

l   Software calibration

l   TVS preponderate over Voltage protect

l   PTC preponderate over Current protect

l   8 channelanalog input module with thermocouple   disconnection detection



Ø   InputChannel:8 differential or 6 differential and 2 single-ended

    (default setting is 6differential and 2 single-ended, can choose by jumper)

Ø   Accepts:

l   J,K,T,E,R,S,B,N,WRe5/26,Land M thermocouples

l   Mollivolt input:±15mV,±50mV,±100mV,±500mV

l   Volt input:±1V and ±2.5V

l   Current input:±20mA(requires a 125Ω resistor)

Ø   Sampling Rate:10 Samples/Second

Ø   Bandwidth:15.7 Hz

Ø   Accuracy:±0.1%

Ø   Zero Drift:0.5µV/°C

Ø   Span Drift:25ppm/°C

Ø   CMR@50/60Hz:150dB

Ø   NMR@50/60Hz:100dB

Ø   Input Impedance:20M Ohms

Ø   Fault and over-voltage protection:With stands over-voltageup to ±35V

Ø   Isolation:3000VDC

Ø   Power Consumption:1.0W

Ø   PowerInput: +10V ~ +30VDC

Ø   Environment

OperatingTemperature -20 ~ 70° C

Humidity5 ~ 95%, non-condensing